Attic Ventilation

Ventilation of the home attic is important for two reasons. During the summer, excess heat that builds up in the attic during the day results in high energy costs for cooling. Also, moisture produced within the home may move into the attic if ceiling vapor barriers are not used. If this moisture is not exhausted from the attic it can condense and cause insulation and construction materials to deteriorate. Thus, temperature and moisture control are the major reasons for providing attic ventilation.

 

Ventilation Quantities

How much attic ventilation is required to provide proper temperature and moisture control? A number of studies sponsored by federal energy funds are under way to look at ventilation rates and methods. However, several studies previously made can help with this decision. The maximum ventilation rate is required to remove heat during the summer cooling months. Attics can reach temperatures of 150 to 160 degrees F during a summer day, although outside air temperatures are only 95 to 97 degrees F. The cooling load for a home air conditioner depends on the difference in temperature between the inside and outside air, and reduction of attic temperatures from 155 degrees to 105 degrees F will result in a significant reduction in cooling load. In a home with poor ceiling insulation, heat movement through ceilings may account for 30 percent or more of the total cooling cost. With a well-insulated ceiling, this source of heat may account for only 12 to 15 percent of the total cooling cost. Thus, high attic ventilation rates are most important for poorly insulated ceilings. A poorly insulated ceiling is one whose R rating is less than 14 or one with fewer than 4 inches of fiberglass, rockwool or cellulose insulation.

Attic temperature depends on the amount of solar radiation, construction details and the rate of ventilation. Calculations indicate that on a July day in Texas, a ventilation rate of one air change per minute for a typical attic using 95-degree F air will lower the peak attic temperature to about 101 degrees F. Providing half air change per minute will lower the temperature to about 106 degrees F. Thus, the first half change per minute is most effective and a doubling of this rate only achieves about 5 degrees F additional cooling. Studies indicate that further increases in ventilation are not effective in significantly reducing attic temperatures.

Winter attic ventilation must be sufficient to remove moisture vapor moving from the living space to the attic. In general, ventilation adequate for summer cooling is more than adequate for winter ventilation. Winter rates need not be more than about a tenth of the summer rate.

Calculate the required summer ventilation rate by determining the volume of attic space and dividing by 2. This will be the cfm (cubic feet per minute) of ventilation air needed. The volume is determined approximately for a rectangular house by multiplying the height from the ceiling to the peak/ridge (H) times the width of the house (W) times the length (L) and dividing by 2 — ( H x W x L / 2 ). For a gable roof, this will be reasonably accurate. For a hip roof house, the volume will be overestimated but adequate.

 

Ventilation Methods

Attic ventilation can be accomplished by gravity ventilators, wind assisted ventilators or power ventilator.. Regardless of the method used, the purpose is to provide uniform ventilation of the attic for proper temperature and moisture control.

Natural ventilation is the most common and energy-efficient method of achieving attic temperature and moisture control. This method takes advantage of two principles. First, as air is heated it becomes less dense and rises. Second, wind movement over and around a home creates areas of high and low pressure. If a space has high air outlets in conjunction with low inlets, ventilation occurs as the air within the space is heated. The greater the vertical distance between the outlet and inlet, the greater the ventilation rate will be. Thus, roof outlets should be at or very near the ridge, and inlets should be under the roof overhang or near the ceiling line.

Ventilation caused by wind pressure differences requires less vent area to achieve the same ventilation rate as ventilation by gravity. One problem with wind ventilation is that the areas of high and low pressure change with wind direction, causing difficulty in locating inlets and outlets so that ventilation will take place regardless of wind direction. The best system is one in which the outlet is near the ridge and the inlets are in the soffit area. The hip roof is best suited to this system, since there is soffit area on all sides of the house. Outlet vents can be provided by roof louvers, gable end louvers, turbine ventilators or continuous ridge vents. These should be constructed so that rain and snow cannot enter. Water leakage is more likely with the turbine ventilator and gable end louver than with fixed roof or ridge ventilators.

Inlet vents may be of the manufactured type, either slotted or perforated, and installed as individual units or in a continuous strip. The slotted opening seems to resist clogging by fibers and dust better than the perforated opening. Screen wire is sometimes used for soffit vents, but again clogging is a problem. In some localities frequent cleaning may be necessary with either type.

 

Providing for Natural Ventilation

Natural ventilation caused by a chimney effect or by wind movement is the most economical ventilation method. The quantity of ventilation air depends on opening size, temperature rise and wind movement.Tests have shown that effective natural ventilation can be achieved by providing inlet and outlet open vent areas of approximately 1 square inch per square foot of attic area, when roof slopes of 3/12 to 5/12 are used. This vent area should be the net open area rather than gross vent size. Some prefabricated vent materials may have only 60 percent net open area. Thus; if a vent area of 10.4 square feet is required, the gross vent area would be 10.4 / 0.6 = 17.3 square feet. [National standards appear to require only 1/2 this amount of open vent area.  The open vent area calculated by these formulas is to be divided roughly equally between inlet and outlet.]

Suppose a 1,500-square-foot home requires the above soffit vent area. If the total soffit length of the home is 100 feet, the vent width for a continuous soffit vent would be (17.3 x 12) / 100 = 2.1 inches. Ventilators should be purchased on the basis of net ventilation opening.

Roof overhangs of 12 inches or more provide ample space for inlet (soffit) vents. Outlet vents should have the same net area as inlet vents. This is easily provided by continuous ridge vents or individual roof vents for gable-roofed homes. The roof ridge length may not be long enough on a hip roof to use a continuous ridge ventilator. In this case, several individual roof vents, well spaced near the ridge, should be used.

 

Power Ventilation

[For a safety and other reasons some authorities discourage the use of power ventilation.]

Power ventilation can be accomplished in two ways. In homes not mechanically cooled (air conditioned) the temperature can be controlled to some extent by the use of attic fans. These fans are usually ceiling mounted in a central hallway so that outside air is pulled through open windows and exhausted through the attic. Sufficient outlets must be installed in the attic to exhaust the air without creating high pressures against which the fan must operate. The net area of attic outlets should be 1/800th of the rated fan volume in cfm and 1/8 inch static pressure. The outlets should be distributed uniformly.

Air conditioned homes can use power attic ventilators by installing an exhaust fan through the roof or in the gable. Inlets for the ventilating air should be at the soffit, or the opposite gable, when no roof overhang exists.

Power ventilators have the advantage of providing good ventilation even when there is no wind. They also provide limited attic temperature control when installed in conjunction with a thermostat. For well-insulated ceilings (i.e. insulation levels of R-19 or above) it is doubtful that a power ventilation can be justified economically.

However, there are some attics which cannot be ventilated by gravity or wind-assisted methods, and in these the power vent is necessary for moisture and temperature control.

For areas of Texas where blowing dust and sand are a problem, consideration should be given to the use of a power ventilator with automatic or motorized inlet louvers which close when the fan is not in operation. Ventilation can be shut off during a dust storm to prevent the buildup of dust and sand in the attic.